Chapter 6
2. FRENIC5000G11S/P11S Series
6-29
6
Basic operation example using built-in Line/Inverter changeover sequence
Operation start
Trip
occurs
Reset
ON
STOP ON
Line
Inverter
Line
Inverter
Line
Inverter
Line
Line
Inverter
Inverter
3-1
(RUN: Operator panel)
3-2
(STOP: Operator panel)
43-M3
(Line/changeover: Operator panel)
MC1X
(Inverter: Primary side)
MC2X
(Inverter: Secondary side)
MC3X
(Line)
OPX
(Operation command)
43-M2X
(Line/Inv changeover signal)
Inverter operation
Line operation
Run
Run
Run
Run
Run
(A)
(B)
(C)
(B)
(C)
(A) Main circuit chatging time + Contactor closing delay timer (0.2s fixed)
(B) Restart time after momentary power failure (H13) + Contactor closing delay timer (0.2s fixed)
(C) Main circuit charging time + Restart time after momentary power failure (H13) + Contactor closing delay timer (0.2s fixed)
Related functions
X1- X9 terminal (Digital input terminal function)
■
E01 X1 terminal function
to
■
E09 X9 terminal function
Y1 - Y5C terminal (Transistor output function)
■
E20 Y1 terminal function (Function select)
to
■
E24 Y5A, Y5C terminal function (Function select)
6
3-wire operation stop command [HLD]
15
Switching operation between line and inverter (50Hz) [SW50]
16
Switching operation between line and inverter (60Hz) [SW60]
Set
value
Function
11
Line/Inv changeover (for 88) [SW88]
12
Line/Inv changeover (for 52-2) [SW52-2]
13
Line/Inv changeover (for 52-1) [SW52-1]
Set
value
Function
■
H13 Auto-restart (Restart time)
Instantaneous switching to another power line (When the
power of an operating motor is cut off or power failure occurs)
creates a large phase difference between the line voltage and
the voltage remaining in the motor, which may cause electrical
or mechanical failure. To rapidly switch power lines, write the
remaining voltage attenuation time to wait for the voltage
remaining in the motor to attenuate. This function operates at
restart after a momentary power failure.
- Setting range: 0.1 to 5.0s
H13
RESTART
NOTE: *1) Operation switch on control panel
*2) Use “X4” when current input is used.
*3) Take countermeasures against momentary power failure
for a signal from “REMOTE”.
*4) T0 is an electronic timer with reset terminal.
*5) AX terminal function is used to make MC2 OFF after
deceleration to a stop.
*6) Retry condition is determined depending on electric facility.
The cut-off switch CP2 should be prepared in this circuit.
Chapter6-13(P26˜29).p65
07.8.9, 12:52
Page 29
Adobe PageMaker 6.5J/PPC
Summary of Contents for FRENIC5000G11S Series
Page 1: ......
Page 2: ......
Page 154: ...3 30 3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC...
Page 166: ...4 12...
Page 182: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 5 16...
Page 212: ...3 12 13 P23 30 65p 07 8 9 12 34 Page 30 Adobe PageMaker 6 5J PPC 6 30...
Page 234: ...MEMO Chapter8 4 P15 p65 07 8 9 12 57 Page 18 Adobe PageMaker 6 5J PPC...
Page 235: ......
Page 236: ......