UFS8000
UF Unit
51
7.10. Integrity test
The “Integrity test” phase can only be switched on and off manually in the “Standby” phase to check
the membrane for any leakages.
A “rest” stage will first of all be switched on.
The actual test can subsequently be started and stopped via manual control.
(“Start Integrity” / “Stop Integrity”).
During the test period, a blue line will be shown that indicates the permissible decrease. The
measured values will be placed in the graph every second. If the measured value exceeds the
permissible limit, this will then be indicated by means of a green line. In the other case, a red line is
displayed.
You may quit the “Integrity test” phase manually from the “rest” stage (“Exit Integrity”).