UFS8000
Components
35
6.8.7. Pressure meter settings
This description cites the properties of pressure measurement in the feed water as an example.
Similar properties apply for other pressure measurements.
The 0-20mA input that is connected to the concerned pressure meter can be selected for the
inventarisation.
The current range of the pressure meter also has to be specified (0-20mA or 4-20mA).
6.8.8. Properties pressure meter
In this window you can set in which unity the measurement value should be displayed.
Furthermore, the measuring range of the measuring cell can be specified. Measured pressure with
minimal current (“Range Min.” between 0,0 and 10.000,0) and measured pressure with maximal
current (“Range Max.” between 0,0 and 10.000,0). We consider that there is a linear characteristic
between the current and the measured pressure for these measurements.