The name of the sub-process can be set. This is because the order of the sub-processes for this
phase is not always identical for every installation.
For each step you can enter which inputs of limits are monitored, which outputs have to be activated
and the time duration of the phase (0-9999 seconds / minutes).
If a time of 0 is entered the corresponding phase will be omitted.
7.6. Backwash 2
The "Backwash 2" phase is used for a 2
nd
backwash cycle. With this you can make a difference for a
“bottom” backwash and a “top” backwash. After a “Filtration” the both backwashes will be started
alternated. Schematically this will looks as follows :
The backwash may comprise a max. of 6 stages each with a time duration of 0-9999 seconds
/minutes.
The name of the sub-process can be set. This is because the order of the sub-processes for this
phase is not always identical for every installation.
If no 2
nd
backwash is desired, the phase may be omitted by turning the phase switch off (no check
mark in “Activate”). If the phase is activated the various stages can be programmed.
For each step you can enter which inputs of limits are monitored, which outputs have to be activated
and the time duration of the phase (0-9999 seconds / minutes).
If a time of 0 is entered the corresponding phase will be omitted.
Summary of Contents for UFS8000
Page 1: ...Controller for ultra filtration plants Operating manual Software version 1 06 UFS8000 ...
Page 7: ...40 Warranty conditions 122 ...
Page 11: ...UFS8000 Picture of front side 4 2 Picture of front side 1 LCD display touch panel ...
Page 115: ...UFS8000 Overview menu 108 30 Overview menu ...
Page 117: ...UFS8000 Terminal Block 110 32 Terminal block connection 32 1 Schematics ...
Page 118: ...UFS8000 Terminal Block 111 ...