30
6.6. Recorder outputs
Through optional prints (ca-3rec), three or six recorder outputs (0-20mA) can be added. If the print is
connected, then the recorder functions will be displayed in the inventory list.(Recorder 1,2,3,4,5 and 6)
Each output can be set separately within a range of 0-20mA or 4-20mA. Which signals are to be
transmitted at the output concerned can be specified next.
All the measured values (e.g. temperature, flow and pressure) can be transmitted to the 0-20mA
output.
“Activate” must be checked in order to transmit a signal. Next, a range can be specified by entering a
minimum and a maximum value. If the measured value of the measurement concerned is lower than
(or equal to) the set minimum value, then a current of 0 mA (if the output is set at a current range of 0-
20mA) or of 4 mA (if the output is set at a current range of 4-20mA) will be transmitted. If the
measured value is higher than (or equal to) the set maximum value, than the output current is 20 mA.
If the measured value is within the set measuring range, then the output current will be calculated. The
characteristic has a linear coherence.
If a signal is transmitted, then the signal concerned will be checked in the list of the recorder output
concerned.
Summary of Contents for UFS8000
Page 1: ...Controller for ultra filtration plants Operating manual Software version 1 06 UFS8000 ...
Page 7: ...40 Warranty conditions 122 ...
Page 11: ...UFS8000 Picture of front side 4 2 Picture of front side 1 LCD display touch panel ...
Page 115: ...UFS8000 Overview menu 108 30 Overview menu ...
Page 117: ...UFS8000 Terminal Block 110 32 Terminal block connection 32 1 Schematics ...
Page 118: ...UFS8000 Terminal Block 111 ...