Configuration Problems
Table 6-2:
Possible cause
Test
Result
Action
No display on control unit
Power input failure
Check 110/220 V selection
switch.
Setting correct
Go to next test.
Setting incorrect
Change setting and go to
next test.
Check power indication LED
in control unit.
LED illuminated
Power OK - go to next possi-
ble cause.
LED not illuminated
Go to next test.
Check fuse in power supply
unit.
Fuse OK
Go to next possible cause.
Fuse blown
Replace fuse.
Power supply failure
Check power rail LEDs in
power supply unit.
All LEDs illuminated
Supplies OK - proceed to
next possible cause.
LEDs not illuminated
Go to next test.
Check fuse in control unit.
Fuse OK
Go to next possible cause.
Fuse blown
Replace fuse.
Connection problem
Check wiring between con-
trol unit and power supply
unit.
Wiring OK
Go to next text.
Incorrect wiring
Correct wiring.
Check ribbon cable connec-
tions in control unit.
Connections OK
Go to next possible cause.
Connections loose
Secure connections
Control unit failure
Contact Rosemount.
Display nonsense on control unit
Microprocessor fault
Reset by interrupting mains
supply.
Fault clears.
No further action
Fault continues.
Go to next possible cause.
Program corruption, failed
micro PCB
Contact Rosemount.
Display message
Waiting for Reference
Reference wave failure
Check wiring between pow-
er supply unit and control
unit and also between pow-
er supply unit and source
unit.
Wiring OK
Go to next text.
Wiring incorrect
Correct wiring.
Check reference wave in
power supply unit -use oscil-
loscope at terminals 4 and 5
37 Hz square wave approx.
12 V - OK
Go to next test.
37 Hz square wave approx.
12 V - not OK
Contact Rosemount.
Check reference wave in
control unit - use oscillo-
scope at terminals 2 and 5.
37 Hz square wave approx.
12 V - OK
Contact Rosemount.
Troubleshooting
Reference Manual
93
Summary of Contents for Rosemount CCO 5500
Page 4: ......
Page 8: ...Contents iv Rosemount CCO 5500 ...
Page 28: ...System Wiring Diagram Figure 2 7 Install 20 Rosemount CCO 5500 ...
Page 32: ...Install 24 Rosemount CCO 5500 ...
Page 88: ...Operation 80 Rosemount CCO 5500 ...
Page 98: ...Maintenance 90 Rosemount CCO 5500 ...
Page 108: ...Troubleshooting 100 Rosemount CCO 5500 ...
Page 110: ...Spare parts 102 Rosemount CCO 5500 ...
Page 122: ...Return equipment to the factory 114 Rosemount CCO 5500 ...
Page 123: ...Return equipment to the factory Reference Manual 115 ...