D.9
Foxboro sensors
D.9.1
Series 1800 sensor to 8732 Transmitter
To connect a Series 1800 sensor to a Rosemount 8732 Transmitter, connect coil drive and
electrode cables as shown in
.
CAUTION!
Do not connect mains or line power to the magnetic flowtube sensor or to the transmitter coil
excitation circuit.
Wiring Diagram for Foxboro Series 1800 and Rosemount 8732
Figure D-13:
17
18
19
3
2
1
L1
L2
A
C
D
E
F
G
H
I
J
B
A.
Electrode connections
B.
Coil connections
C.
White lead
D.
White shield
E.
Black lead
F.
Inner shield
G.
Black shield
H.
Outer shield
I.
Any shield
J.
Chassis ground
Note
for actual terminal block configuration drawing.
Foxboro Series1800 Sensor Wiring Connections
Table D-13:
Rosemount 8732
Foxboro Series 1800 sensors
1
L1
Implementing a Universal Transmitter
Reference manual
233
Summary of Contents for Rosemount 8732EM
Page 2: ......
Page 6: ...Contents iv Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 10: ...Safety messages 4 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 14: ...Introduction 8 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 30: ...Sensor Installation 24 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 92: ...Operation 86 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 158: ...Maintenance 152 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 214: ...Product Certifications 208 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 217: ...Wiring 8732EM using combination cable Figure C 2 Wiring Diagrams Reference manual 211 ...
Page 222: ...Wiring Diagrams 216 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 253: ...Implementing a Universal Transmitter Reference manual 247 ...