Time limit
LOI menu path
Detailed Setup > Signal Processing > Main Config DSP > Time
Limit
The time limit parameter forces the output and running average values to the new value of
an actual flow rate change that is outside the percent limit boundaries. It thereby limits
response time to flow changes to the time limit value rather than the length of the running
average. If the number of samples selected is 100, then the response time of the system is
10 seconds. In some cases this may be unacceptable. Setting the time limit forces the
transmitter to clear the value of the running average and re-establish the output and
average at the new flow rate once the time limit has elapsed. This parameter limits the
response time added to the loop. A suggested time limit value of two seconds is a good
starting point for most applicable process fluids. This parameter can be configured for a
value between 0.6 and 256 seconds. The default value is 2 seconds.
10.6
Explanation of signal processing algorithm
An example plotting flow rate versus time is given below to help visualize the signal
processing algorithm.
Digital Signal Processing
138
Rosemount
®
8732EM Transmitter with HART Protocol Reference Manual
Summary of Contents for Rosemount 8732EM
Page 2: ......
Page 6: ...Contents iv Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 10: ...Safety messages 4 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 14: ...Introduction 8 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 30: ...Sensor Installation 24 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 92: ...Operation 86 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 158: ...Maintenance 152 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 214: ...Product Certifications 208 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 217: ...Wiring 8732EM using combination cable Figure C 2 Wiring Diagrams Reference manual 211 ...
Page 222: ...Wiring Diagrams 216 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 253: ...Implementing a Universal Transmitter Reference manual 247 ...