Empty pipe (EP) trigger level
LOI menu path
Diagnostics > Basic Diag > Empty Pipe > EP Trig Level
Limits: 3 to 2000
Empty pipe trigger level is the threshold limit that the empty pipe value must exceed
before the empty pipe diagnostic alert activates. The default setting from the factory is
100.
Empty pipe (EP) counts
LOI menu path
Diagnostics > Basic Diag > Empty Pipe > EP Counts
Limits: 2 to 50
Empty pipe counts is the number of consecutive updates that the transmitter must receive
where the empty pipe value exceeds the empty pipe trigger level before the empty pipe
diagnostic alert activates. The default setting from the factory is 5.
9.3.2
Optimizing tunable empty pipe
The tunable empty pipe diagnostic is set at the factory to properly diagnose most
applications. If this diagnostic activates, the following procedure can be followed to
optimize the empty pipe diagnostic for the application.
Procedure
1.
Record the empty pipe value with a full pipe condition.
Example:
Full reading = 0.2
2.
Record the empty pipe value with an empty pipe condition.
Example:
Empty reading = 80.0
3.
Set the empty pipe trigger level to a value between the full and empty readings.
For increased sensitivity to empty pipe conditions, set the trigger level to a value
closer to the full pipe value.
Example:
Set the trigger level to 25.0
4.
Set the empty pipe counts to a value corresponding to the desired sensitivity level
for the diagnostic.
Advanced Diagnostics Configuration
114
Rosemount
®
8732EM Transmitter with HART Protocol Reference Manual
Summary of Contents for Rosemount 8732EM
Page 2: ......
Page 6: ...Contents iv Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 10: ...Safety messages 4 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 14: ...Introduction 8 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 30: ...Sensor Installation 24 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 92: ...Operation 86 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 158: ...Maintenance 152 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 214: ...Product Certifications 208 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 217: ...Wiring 8732EM using combination cable Figure C 2 Wiring Diagrams Reference manual 211 ...
Page 222: ...Wiring Diagrams 216 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 253: ...Implementing a Universal Transmitter Reference manual 247 ...