A.3.1
Functional specifications
Service
Conductive liquids and slurries
Line sizes
½
–in. to 36-in. (15 mm to 900 mm)
Sensor coil resistance
7 - 16 Ω
Interchangeability
Rosemount 8705-M sensors are interchangeable with 8712EM and 8732EM transmitters.
Rosemount 8750W sensors are interchangeable with 8750W transmitters. System
accuracy is maintained regardless of line size or optional features. Each sensor nameplate
has a sixteen-digit calibration number that can be entered into a transmitter through the
Local Operator Interface (LOI) or the Field Communicator.
Upper range limit
39.37 ft/s (12 m/s)
Ambient temperature limits
•
–20 to 140 °F (–29 to 60 °C) standard design
•
–58 to 140 °F (–50 to 60 °C) with "SH" all stainless design
Pressure limits
See
Vacuum limits
PTFE lining
Full vacuum to 350 °F (177 °C) through 4-in. (100 mm) line sizes. Consult
Technical Support for vacuum applications with line sizes of 6 inches (150
mm) or larger
All other standard sen-
sor lining materials
Full vacuum to maximum material temperature limits for all available line
sizes.
Submergence protection IP68
The remote mount sensor is rated IP68 for submergence to a depth of 33 ft (10 m) for a
period of 48 hours. IP68 rating requires that the transmitter must be remote mount.
Installer must use IP68 approved cable glands, conduit connections, and/or conduit plugs.
For more details on proper installation techniques for IP68, reference Rosemount
Technical Note 00840-0100-4750 available on www.rosemount.com.
(6) Not available for Class/Div approval codes N5, N6, K5, KU.
Product Specifications
Reference manual
195
Summary of Contents for Rosemount 8732EM
Page 2: ......
Page 6: ...Contents iv Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 10: ...Safety messages 4 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 14: ...Introduction 8 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 30: ...Sensor Installation 24 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 92: ...Operation 86 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 158: ...Maintenance 152 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 214: ...Product Certifications 208 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 217: ...Wiring 8732EM using combination cable Figure C 2 Wiring Diagrams Reference manual 211 ...
Page 222: ...Wiring Diagrams 216 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 253: ...Implementing a Universal Transmitter Reference manual 247 ...