NAMUR Values
(continued)
Table 8-2:
Low
3.8 mA
3.5 mA
High
20.5 mA
22.6 mA
AO diagnostic alarm
LOI menu path
Detailed Setup > Output Config > Analog > AO Diag Alarm
There are diagnostics that, when under active conditions, do not drive the analog output
to alarm level. The AO diagnostic alarm menu enables selection of these diagnostics to be
associated with an analog alarm. If any of the selected diagnostics are active, it will cause
the analog output to go to the configured alarm level. For a list of diagnostic alarms that
can be configured to drive an analog alarm, see
.
Analog Alarm Diagnostic Options
Table 8-3:
Diagnostic
Description
Empty Pipe
Drive to an alarm state when empty pipe is detected.
Reverse Flow
Drive to an alarm state when reverse flow is detected.
Grounding / Wiring Fault
Drive to an alarm state when grounding or wiring fault is detec-
ted.
High Process Noise
Drive to an alarm state when the transmitter detects high levels
of process noise.
Electronics Temperature Out of
Range
Drive to an alarm state when the temperature of the electronics
exceeds allowable limits
Electrode Coating Limit 2
Drive to an alarm state when electrode coating reaches a point
where it impacts the flow measurement
Totalizer Limit 1
Drive to an alarm state when the totalizer value exceeds the pa-
rameters set in the totalizer limit configuration (see page 5-x for
more details on this functionality)
Flow Limit 1
Drive to an alarm state when the flow rate exceeds the parame-
ters set in the flow limit 1 configuration (see page 5-x for more
details on this functionality)
Flow Limit 2
Drive to an alarm state when the flow rate exceeds the parame-
ters set in the flow limit 2 configuration (see page 5-x for more
details on this functionality)
Advanced Configuration Functionality
Reference manual
89
Summary of Contents for Rosemount 8732EM
Page 2: ......
Page 6: ...Contents iv Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 10: ...Safety messages 4 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 14: ...Introduction 8 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 30: ...Sensor Installation 24 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 92: ...Operation 86 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 158: ...Maintenance 152 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 214: ...Product Certifications 208 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 217: ...Wiring 8732EM using combination cable Figure C 2 Wiring Diagrams Reference manual 211 ...
Page 222: ...Wiring Diagrams 216 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 253: ...Implementing a Universal Transmitter Reference manual 247 ...