CAUTION!
Do not connect mains or line power to the magnetic flowtube sensor or to the transmitter coil
excitation circuit.
Wiring Diagram for Brooks Sensor Model 5000 and Rosemount 8732
Figure D-4:
1
2
17
19
18
3
SHLD
ELECTRODES
+ -
COILS
+ -
G
ND
A
B
A.
Brooks Model 5000
B.
Rosemount 8732 transmitter
Note
Refer to
for actual terminal block configuration drawing.
Brooks Model 5000 Sensor Wiring Connections
Table D-4:
Rosemount 8732
Brooks sensors Model 5000
1
COILS (+)
2
COILS (-)
3
COILS (GND)
17
ELECTRODES (SHLD)
18
ELECTRODES (-)
19
ELECTRODES (+)
D.6.2
Model 7400 sensor to 8732 Transmitter
To connect a Model 7400 sensor to a Rosemount 8732 Transmitter, connect coil drive and
electrode cables as shown in
.
Implementing a Universal Transmitter
224
Rosemount
®
8732EM Transmitter with HART Protocol Reference Manual
Summary of Contents for Rosemount 8732EM
Page 2: ......
Page 6: ...Contents iv Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 10: ...Safety messages 4 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 14: ...Introduction 8 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 30: ...Sensor Installation 24 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 92: ...Operation 86 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 158: ...Maintenance 152 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 214: ...Product Certifications 208 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 217: ...Wiring 8732EM using combination cable Figure C 2 Wiring Diagrams Reference manual 211 ...
Page 222: ...Wiring Diagrams 216 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 253: ...Implementing a Universal Transmitter Reference manual 247 ...