Taylor Series 1100 Sensor Wiring Connections
(continued)
Table D-20:
Rosemount 8732
Taylor Series 1100 sensors
19
E2
D.13.2
Taylor sensor to 8732 Transmitter
To connect a Taylor sensor to a Rosemount 8732 Transmitter, connect coil drive and
electrode cables as shown in
.
CAUTION!
Do not connect mains or line power to the magnetic flowtube sensor or to the transmitter coil
excitation circuit.
Generic Wiring Diagram for Taylor Sensors and Rosemount 8732
Figure D-21:
C
A
B
D
E
F
G
17
18
19
3
2
1
E2
E1
S1 and S2
A.
Taylor sensor
B.
Rosemount 8732 transmitter
C.
Electrode connections
D.
Coil connections
E.
Green
F.
White
G.
Black
Note
Refer to
for actual terminal block configuration drawing.
Taylor Sensor Wiring Connections
Table D-21:
Rosemount 8732
Taylor sensors
1
Black
2
White
3
Green
Implementing a Universal Transmitter
242
Rosemount
®
8732EM Transmitter with HART Protocol Reference Manual
Summary of Contents for Rosemount 8732EM
Page 2: ......
Page 6: ...Contents iv Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 10: ...Safety messages 4 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 14: ...Introduction 8 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 30: ...Sensor Installation 24 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 92: ...Operation 86 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 158: ...Maintenance 152 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 214: ...Product Certifications 208 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 217: ...Wiring 8732EM using combination cable Figure C 2 Wiring Diagrams Reference manual 211 ...
Page 222: ...Wiring Diagrams 216 Rosemount 8732EM Transmitter with HART Protocol Reference Manual ...
Page 253: ...Implementing a Universal Transmitter Reference manual 247 ...