Automatic
CasaConnect KNX Control Center
• Version: 13.09.2021 • Technical changes and errors excepted.
If you want to change the periods, touch the tool icon.
6.3.3. Set time switch period, Page 106
Shut-off times prevent the windows, for example, from opening and closing at night,
and thus causing noise. Note that night back cooling is not possible during the set pe-
riod.
Wind sensor:
Shows the delay for the wind sensor. Touch the field to select the sensor (if there are
several wind sensors), and to set how long the wind limit value must be exceeded be-
fore the wind alarm is triggered.
Default setting: 5 s.
Wind ventilation:
Shows whether the window remains ajar when it is windy. This setting is only active
when the wind alarm has been switched on. Touch the field in order to switch gap
opening on or off if there is a wind alarm.
With gap opening, the window can still be opened slightly despite a wind alarm.
Wind ventilation: Direction:
Shows the wind direction, for when wind ventilation opens. The setting is only active
if wind ventilation has been switched on. Tap the field and set the direction, from which
the wind is coming.
Default setting: 0° to 360°.
Wind ventilation: Position:
Shows the position to which the window opens for wind ventilation. The setting is only
active if wind ventilation has been switched on. Touch the field and set the open posi-
tion (0% = closed, 100% = fully open).
Default setting: 15%.
Wind alarm:
Shows the value, from which the wind alarm is triggered. Touch the field and set the
wind speed.
Default setting: 8.0 m/s.
If the window should not react to wind, switch the wind alarm
OFF
.
The wind alarm protects the system and equipment from damage by closing the win-
dow. Manually opened windows are also closed if there is a wind alarm.
A wind alarm actuated for the motor will remain active for 5 minutes. If the saved value
is exceeded in these 5 minutes, the stoppage time will be restarted.