65
Basic settings in the ETS
CasaConnect KNX Control Center
• Version: 13.09.2021 • Technical changes and errors excepted.
Setpoint Eco
Eco mode is usually used for night mode.
If setpoints are set separately:
A temperature range is defined, in which the set point can be modified.
When heating and cooling are used:
Set the evaluation of the status object here.
Fan coil control
The fan coil control enables the fan of convector heating/cooling systems to be con-
trolled.
Activate the fan coil control.
Select whether the first fan step should also be switched on if the second and third
steps are running and whether the second fan should also be switched of if the third
step is running.
4.4.
Symbol overview
The following icons are stored in the internal library of the
CasaConnect KNX
:
Lighting
Min. object value heating/cooling (in 0.1 °C)
-300…800; 160
Max. object value heating/cooling (in 0.1
°C)
-300…800; 280
Evaluation of the status object
• 0 = Heating | 1 = Cooling
• 1 = Heating | 0 = Cooling
Use fan coil control
No •
Yes
Switch on level 1 also for level 2 to 3
No • Yes
Switch on level 2 also for level 3
No • Yes
0001
Ceiling lights
on
0002
Ceiling lights
off
0003
Direct lights
on
0004
Direct lights
off
0005
Wall lights
on