![Elsner 71200 Installation, Setting, Operation Download Page 117](http://html1.mh-extra.com/html/elsner/71200/71200_installation-setting-operation_2396535117.webp)
115
Automatic
CasaConnect KNX Control Center
• Version: 13.09.2021 • Technical changes and errors excepted.
Timed closing: Actuation position:
Shows the actuation position in percent for the time closing, also the slat position for
blinds. Touch the field to set the position using a slider. Actuation position: 0% = fully
retracted, 100% = fully extended.
Default setting: 100%.
Slat position: 0% = horizontal, 100% = closed.
Default setting: 100%
Outdoor temperature:
Shows the setting for the outside temperature block. Touch the field to adjust the block.
Select
OFF
if the shading should depend on the outside temperature (default setting).
Change to
ON
to set the desired temperature.
Default setting: 5.0°C.
The block is lifted again only when the temperature rises more than 2.0 °C over the pre-
set value (hysteresis).
The block only applies to automatic operation; no shading based on light intensity or
the position of the sun takes place. The motor also reacts to the wind alarm, rain alarm
and manual movement commands if the outside temperature block is active.
Note that the running rails of the shades or other mechanical parts may still be frozen,
even if the outdoor temperature has climbed to quite high values.
ATTENTION
Property damage due to movement of frozen-solid shades!
Motor and curtain can be damaged if a
frozen solid outside shade is moved.
•
Use the frost alarm function to achieve reliable protection against
damage due to icing.
Outdoor temperature: Behaviour:
Shows the behaviour of the shades if the outdoor temperature lock is triggered. The
setting will only be activated once an outdoor temperature has been set.
Select whether the shades should be retracted if the outdoor lock temperature is un-
dercut.
If
Yes
(retract), the shade is retracted after the end of the travel delay time (default)
If
Non
(do not move), the shade remains in the current position. When the rain or wind
alarm is triggered, the shade will still be retracted (the alarm has priority over temper-
ature block).
Timed opening:
Touch the field to select periods when the shade should be retracted. Enable one or
more periods in the list.