MP500/4N-8-16 Programming
37
4.11.4
Isolable
An input set a
s “isolable” will be subject to manual and automatic isolations.
Input isolation and end of isolation
IMPORTANT!
The input partition mode must be SYS ARM BLOCK to be EN50131 compliant.
IMPORTANT!
Inputs programmed as “Delayed”, “First Entry”, “Way”, “Last Exit” and “First Entry/Last Exit” must not be
programmed as “isolable”. Failure to respect this requirement may cause anomalous behaviour in the system.
4.11.5
Ancillary functions (Gong, Courtesy Light, Door Opener, Absence of Move)
Ancillary functions which can be used when the system is disarmed can be associated to the burglar inputs.
The ancillary functions only work if all the partitions assigned to the input are disarmed.
See
Installation Manual
for more details on the single functions.
These functions are not EN50131 compliant because they are not described in the standard.
Only one of the following ancillary function options may be selected for each input: None, Absence of Move, Gong, Courtesy Light,
Door Opener.
4.11.6
Burglar input attributes (Release Type, AND / OR partitions)
This function is EN50131 compliant.
The operation of the burglar inputs may be customised further by setting the attributes.
The
Release Type
determines when the alarm signal is generated. Possible settings:
Single release
: the alarm is generated as soon as the input is open.
Double release
: the alarm is generated at the end of the second event only if this occurs within 120 seconds from the first one.
IMPORTANT!
The input partition mode must be SYS ARM BLOCK to be EN50131 compliant.
Common input
this determines what happens to an input which belongs to more than one partition. Possible settings:
AND Partitions
: this creates a logical connection between the partitions to which the input belongs and the alarm is generated
only if all partitions are armed.
OR Partitions
: this creates a logical connection between the partitions to which the input belongs and the alarm is generated if
at least one partitions is armed.
4.11.7
AND inputs
This function is EN50131 compliant.
This creates a logical connection between two burglar inputs with the same customisation. The alarm is generated only if both are kept
open within 5 minutes from one another (the first input to be opened may be closed again in the meantime). The five minute interval
cannot be edited.
See the
Installation Manual
for more information.
4.11.8
Programming procedure
IMPORTANT!
Changes to the default customisations of the control panel inputs could cancel EN50131 compliance.
Proceed as follows to program the inputs:
1) Enter
<Installer code>
, press
, then
and finally
repeatedly until PROGRAMMING
appears.
2) Press
and then press
several times until INPUTS appears.
3) Press
.
4) Press
.
5) Press
and
to select the required input. Press
to confirm.
UT00:INSTALLER
PROGRAMMING
PROGRAMMING
INPUTS
INPUTS
CONTROL PANEL
CONTROL PANEL
UC.In1: In001
UC.In1: In001
LOGIC NUMBER
Summary of Contents for MP500/16