MP500/4N-8-16 Programming
31
7) Press
.
8) Enter the date dd/mm/yy format directly using the number keys using an initial 0 if needed. If you
make a mistake, press
and access the SET DATE menu.
9) Press
to confirm the entered date then
.
10) Press
. You can now choose to automatically update summer time/standard time.
In the European Union, summer time starts on the last Sunday of March and ends on the last
Sunday of October. To change automatically, press
repeatedly until ENABLE appears.
11) Press
to confirm the entered setting then
.
12) Press
. Enter the month for shifting from summer time to standard time (10 = October for the
European Union). Enter the month directly using the number keys.
13) Press
to confirm the month then
.
14) Press
. Enter the month for shifting from standard time to summer time (3 = March for the
European Union). Enter the month directly using the number keys.
15) Press
to confirm the month then
.
16) Press
. Select the Sunday (LAST SUNDAY or FIRST SUNDAY) with the
and
on when
to shift time (the last Sunday of the month in the European Union) and press
to confirm the
selection.
17) Press
repeatedly to exit from the menu.
4.9
PARTITION PROGRAMMING
The MP500/4N control panel can manage up to four partitions, the MP500/8 control panel up to eight and the MP500/16 control panel
can manage up to 16 partitions. The actual number of partitions is established during the programming procedure. Each system must
have at least one partition.
System inputs, outputs, keypads and readers can be freely assigned and belong to more than one partition.
The arming mode can be programmed for each partition so that some burglar inputs remain open when the system is armed:
Sys arm block
: a partition programmed in this way cannot be armed if any assigned inputs are open.
Standard
: an alarm is generated if any assigned inputs are open when the partition is armed.
Self Inhibition
: the burglar inputs assigned to the partition which can be isolated and are open when the partition is
armed will be automatically isolated (no more than 70% of the inputs assigned to the partition will be isolated; any
inputs in excess will remain open and generate an alarm). The isolated inputs will automatically end insulation if they
are closed again.
In other words, the system can be armed if there are open inputs in a standard partition, it cannot be armed if there are open inputs in a
Sys Arm Block partition and it can always be armed if there are open inputs in a Self Inhibition partition but an alarm will be tripped if
there are too many open inputs.
SET DATE
DATE 12/01/14
HOUR - DATE
SUMMER TIME
SUMMER TIME
ENABLE
HOUR - DATE
LEGAL T. MONTH
LEGAL T. MONTH
10
HOUR - DATE
SUMMER T. MONTH
SUMMER T. MONTH
3
HOUR - DATE
SUNDAY
SUNDAY
LAST SUNDAY
MP500/16
12/01/2014 10:10