MP500/4N-8-16 Programming
121
9.5.2
Control panel upgrade procedure at power on
Proceed as follows to upgrade the control panel:
1. Remove all power from the control panel (remove main power and disconnect the back-up battery).
2. Plug the IT USB/KEY interface into the J11 connector of the control panel.
3. Insert the USB memory stick, onto which the upgrade file was previously copied (.bin), into the USB port of the IT USB/KEY
interface.
4. Power the control panel again (mains power and back-up battery).
Note
: Implement the appropriate actions to block any fail-safe siren commands or otherwise disconnect the power by removing the
internal back-up batteries.
The control panel will be upgraded at power on and the new firmware will be downloaded. The upgrade procedure may last for a few
minutes.
IMPORTANT!
Do not remove the flash drive until the upgrade procedure is completed.
After upgrading, one of the following indications will appear according to the result type.
Positive result.
The procedure was successful.
The run LED will light
up on the control panel according to the “Successful Update” sequence (off for 2 seconds - blinking for 2
seconds).
IMPORTANT!
This indication will appear even if the procedure never started.
No device can be upgraded or the devices have the same upgr
ade file release (“filename”.BIN).
Negative result
. The procedure was interrupted or is not OK.
The run LED will light up on the control panel according to the “Update was not successful” sequence (on for 2 seconds - blinking
for 2 seconds).
IMPORTANT!
This indication will also appear if one of the following errors occurs:
o
The USB memory stick does not respond.
o
The file (.bin) is not in the root of the USB memory stick.
The control panel will maintain one of the two indication sequences until the control panel power off.
To make the upgrade definitive and return the system to operating conditions:
1. Remove all power from the control panel (remove main power and disconnect the back-up battery).
2. Unplug the IT USB/KEY interface from the J11 connector of the control panel.
3. Power the control panel again (mains power and back-up battery).
Details on the firmware upgrading procedure will be saved in the Event Log in both cases at the end of the operation.