Appendix B: Transmitter Installation
iConnect Installation Manual
86
An additional battery can be placed inside the detector (EL-4745). To insert the additional
battery open the front cover and place the battery. Pay attention to the polarity.
Installation Procedure
To install PIR detectors:
Before permanently mounting the detector, test the transmitter from the exact mounting
position. If necessary, improve the position of the transmitter. The recommended height is
2.2m (6.6 ft).
1.
Knock out the mounting holes of the mounting bracket and attach it to the wall.
2.
To use the rear tamper switch, insert a screw into the rear tamper mounting hole located in the center of the
bracket. When the bracket is removed from the wall, the screw causes the tamper release to break away from
the bracket and the rear tamper switch is released
3.
Align the pins on the mounting bracket with the slots on the detector's base, attach the EL-4745PI to the bracket and
slide it down while gently pressing it to fit to its place.
4.
Attach the screw provided in the detector kit to the bottom of the mounting bracket.
Operation Modes
Warm-Up Time
The detector will need to warm up for the first 90 seconds after applying power.
Walk Test Mode
A walk test is performed in order to determine the lens coverage pattern of the detector. Walk Test mode cancels the
delay time between detections, enabling you to perform an efficient walk test.
To perform a Walk Test:
1.
Set the iConnect Control System to Walk test mode (Quick key [7034]).
2.
Walk across the scope of the detector according to the detection pattern selected.
3.
Confirm that the LED activates and deactivates accordingly. Wait for ten seconds, after each detection, before
continuing the test.
4.
After completing the walk test set the system to normal operation mode.
LED Indication
The LED indicator is lit every time a transmission is made. The Led can be enabled / disabled by programming.
LED should only be disabled after successfully walk testing the detector.
Parameters Setting Procedure
As a 2-Way detector, the EL-4745PI parameters can be modified only from the iConnect Control System.
In comparison to other detectors the EL 4745PI has dedicated parameters that can be modified under quick key 9>1>1>11
•
LED Enable: On/Off (Default: On)
•
Pulse count: The pulse counter determines the amount of beams that need to be crossed before the detector
will produce an alarm.
•
Alarm Delay: The delay between reporting detections to the main unit.
Battery Replacement
In case of a low battery (2.5 VDC or less), the detector low battery condition is reported to the system and low battery
message is displayed.
To replace the battery:
Open the battery compartment door located on the back cover, replace the battery, and close the compartment door.
Attach the EL-4745PI to the bracket and slide it down while gently pressing it to fit to its place.
Summary of Contents for iconnect
Page 79: ...Appendix A Menu Structure iConnect Installation Manual 75 ...
Page 80: ...Appendix A Menu Structure iConnect Installation Manual 76 ...
Page 81: ...Appendix A Menu Structure iConnect Installation Manual 77 ...
Page 82: ...Appendix A Menu Structure iConnect Installation Manual 78 ...
Page 83: ...Appendix A Menu Structure iConnect Installation Manual 79 ...
Page 84: ...Appendix A Menu Structure iConnect Installation Manual 80 ...