12 Appendix
12.3 Technical data
344
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
12.3 Technical data
Any data that is different for the easy800 standard and easy800-SWD is
presented separately. Otherwise the information is valid for all easy800
devices.
12.3.1 Standards
12.3.2 General ambient conditions
easy800
Standards
EN 55011, EN 50178, EN 61131-2, IEC EN 61000-4,
IEC60068-2-6, IEC60068-2-27
Ambient climatic conditions
Cold to IEC 60068-2-1, heat to IEC 60068-2-2, damp heat, constant, to IEC 60068-2-78; cyclical to IEC 60068-2-30,
temperature change to IEC68000-2-14
Operating ambient temperature
°C,
(°F)
–25 to +55 (–13 to +131)
Condensation
Prevent condensation by means of suitable measures
LCD display (reliably legible)
°C,
(°F)
0 to +55, (–32 to +131)
Storage
°C,
(°F)
–40 to +70, (–40 to +158)
Relative humidity, non-
condensing (IEC/EN 60068-2-30)
%
5 to 95
Air pressure (in operation)
hPa
795 up to 1080
Ambient mechanical conditions
Protection type EN 50178,
IEC 60529, VBG4
IP20
Vibrations (IEC EN 60068-2-6)
constant amplitude
easy800 standard:0.15 mm
easy800-SWD: 3.5 mm
Hz
easy800 standard: 10 - 57
easy800-SWD: 5 - 8.4
constant acceleration
easy800 standard: 2 g
easy800-SWD: 1 g
Hz
easy800 standard: 57 - 150
easy800-SWD: 8.4 - 150
Mechanical shock resistance
(IEC EN 60068-2-27) semi-
sinusoidal 15 g/11 ms
Shocks
18
Drop (IEC EN 60068-2-31)
Drop
height
mm
50
Free fall, packaged
(IEC/EN 60068-2-32)
m
easy800 standard: 1
easy800-SWD: 0.3
Electromagnetic compatibility (EMC)
Electrostatic discharge (ESD),
to IEC EN 61000-4-2