User Information

  

B01 

B101 

 

E61-136-00 

 

• 

Indication of the switching state via LED 

• 

2 start behaviors possible: 
- Monitored manual start 
-  Automatic start 

• 

Up to PL e, SILCL 3, category 4 

• 

It is not allowed to open the device, tamper with the devi-
ce or bypass the safety devices. 

• 

All relevant safety regulations and standards are to be 
observed. 

• 

The overall concept of the control system in which the 
device is incorporated must be validated by the user. 

• 

Failure to observe the safety regulations can result in 
death, serious injury and serious damage. 

Correct Use 

The SR2C is a universal emergency stop safety switching device 

with two safe relay outputs that can quickly and safely stop the 

moving parts of a machine or system in case of danger.  

Applications for the SR2C include single or dual-channel emer-

gency stop circuits and guard monitoring on machines and sys-

tems. 

Features 

• 

2 safe, redundant relay outputs 

• 

Connection of: 

• 

    -  Emergency stop buttons 
    -  Safety switches 
    -  Non-contact safety switches 
    -  OSSD-Outputs 

• 

Single and dual-channel operation possible 

• 

Feedback loop for monitoring downstream contactors or 
expansion modules 

• 

Cyclical monitoring of the output contacts 

Function 

The emergency stop safety switching device SR2C is 
designed for safe isolation of safety circuits according to 
DIN EN 60204-1 and can be used up to safety category 4, 
PL e according to EN ISO 13849-1. 
The internal logical system closes the safety contacts when 
the start button is pressed. 
If the emergency stop circuit is opened, the positively 
driven safety contacts are opened and safely switch the 
machine off. It is ensured that a single fault does not lead 
to a loss of the safety function and that every fault is detec-
ted by cyclical self-monitoring no later than when the sys-
tem is switched off and switched on again. 

Electrical  
Connection 

• 

When the 24V version is used, a control transformer 
according to EN 61558-2-6 or a power supply unit with 
electrical isolation from the mains must be connected. 

• 

External fusing of the safety contacts (4A slow-blow or 
6A quick-action or 10A gG) must be provided. 

• 

A maximum length of the control lines of 1000 meters 
with a line cross section of 0.75 mm

2

 must not be excee-

ded. 

• 

The line cross section must not exceed 2.5 mm

2

• 

If the device does not function after commissioning, it 
must be returned to the manufacturer unopened. Ope-
ning the device will void the warranty. 

Installation 

As per DIN EN 60204-1, the device is intended for installa-
tion in control cabinets with a minimum degree of protection 
of IP54. It is mounted on a 35-mm DIN rail according to 
DIN EN 60715 TH35. 

Safety Precautions 

• 

Installation and commissioning of  the device must be 
performed 

only by authorized personnel

• 

Observe the country-specific regulations when installing 
the device. 

• 

The electrical connection of the device is only allowed to 
be made with the device isolated. 

• 

The wiring of the device must comply with the instructi-
ons in this user information, otherwise there is a risk that 
the safety function will be lost. 

Fig. 1 Block diagram SR2C 

Fig. 2 Installation/removal 

Fig. 3 Connections 

A1: 

 Power supply 

A2. 

 Power supply 

S11:  

DC 24V control voltage 

S10:  

Control line 

S21:  

Start control line 

S13:  

Control line 

S14:  

Control line 

S12:  

Control line 

13-14:  

Safety contact 1 

23-24:  

Safety contact 2 

Safety Emergency Stop Relay SR2C 

English translation 

(not for plug-in terminals) 