5 Function blocks
5.26 PT - Put value to the NET
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
235
5.26 PT - Put value to the NET
The PUT function block PT.. enables you to transfer a 32-bit operand to the
NET. The operand value is transferred and automatically read by the
corresponding GET function block GT of another NET station.
easy800 device allows the use of up to 32 PUT function blocks.
EASY802-DC-SWD is not provided for the function block.
Contacts and Coils
1) These outputs are available for EASY806-DC-SWD from device version 01 and for easy800 standard from device
version 07.
Example of a PUT function block:
Figure 168:Wiring the trigger coil
The trigger coil is connected to a device input.
Figure 169:Wiring the function block contacts
The contacts transfer the function block information to markers.
Parametric programming of the function block inputs/outputs
When using the function block in the circuit diagram for the first time, use
OK to automatically enter the general display of function block parameters,
as shown in the figure on the left. Enter the function block settings here.
The display contains the following elements:
Contacts
Meaning
PT..Q1
The trigger coil is active
PT..AC
The temporary storage and subsequent transfer of the input value to the NET. 1).
PT..E1
A transfer error.
1)
Coils
Function
PT..T
_
Trigger coil, on a rising edge the function block temporarily stores the input value and transfers it
to the NET
I 05--------------------------
Ä
PT07T_
PT07Q1---------------------------
Ä
M 11
PT07AC---------------------------
Ä
M 22
PT07E1---------------------------
Ä
M 33
PT07 -
>I1
PT07
Function block: PUT, number 07
-
Parameter display: Call not enabled
>I1
Input value that is to be put onto the NET:
-2147483648 - 2147483647