5 Function blocks
5.4 BT, Data block Transformer
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
149
5.4 BT, Data block Transformer
This function block is available for easy800-SWD from device version 01 and
for easy800 standard devices from device version 04.
The block transfer function block (BT) is used for transferring values from one
marker range to another (copy data). The marker ranges can be overwritten
with a particular value (data initialization). The following marker ranges can be
transferred and written:
•
MB.
•
MW.
•
MD.
easy800 device allows the use of up to 32 data block transfer function
blocks.
Contacts and Coils
Example of a block transfer function block
Figure 107:Wiring the trigger coil
The trigger coil is connected to a device input.
Figure 108:Wiring the contacts
The messages of the function block are sent as a group message to a
marker.
Parametric programming of the function block inputs/outputs
When using the function block in the circuit diagram for the first time, use
OK to automatically enter the general display of function block parameters,
as shown in the figure on the left. Enter the function block settings here.
The display contains the following elements:
Contacts
Meaning
BT..E1
Outside of source or destination range
BT..E2
Overlapping of source and destination range
BT..E3
Invalid offset
Coils
Function
BT..T
_
Triggering the transfer on a rising edge
I 05--------------------------
Ä
BT07T
_
BT07E1
o
BT07E2
s
BT07E3
j
-----------------------
Ä
M 42
BT07 INI +
>I1
>I2
>NO