2 Installation
2.4 Connecting the power supply
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
29
Figure 18:Power supply at easy800-SWD
DC expansion unit EASY…-DC-.E
Figure 19:Power supply on the DC expansion unit
→
easy800 standard DC version, the expansion units as well as
easy800-SWD are protected against reverse polarity.
L01-
F1
L01+
F2
24 V
0 V
AUX
24 V
0 V
POW
U
e
= 24 V DC
(20.4 - 28.V DC)
802: I
e
= 400 mA
806: I
e
= 700 mA
F1 ≧ 3 A
UL: F2 ≦ 2 A
IEC: F2 ≦ 3 A
0V
0V
24V
L01-
F1
L01+
E+
E-
R1
...
R12
24 V
H