12 Appendix
12.3 Technical data
356
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
Inductive load without external suppressor circuit
General explanations: T
0.95
= time in milliseconds until 95 % of the stationary
current is reached
easy800 standard:
Utilization categories in groups Q1 to Q4, Q5 to Q8
Short-circuit protective device
Electronic
(evaluation possible via diagnostic input I16)
easy800 standard: yes (Q1 – Q4)
easy800-SWD: yes (Q1/Q2)
thermal
(evaluation possible via diagnostic input I15)
easy800 standard: yes (Q5 – Q8)
easy800-SWD: no
Short-circuit tripping current for R
a
10 m
Ω
(depending on number of active channels and
their load)
A
easy800 standard: 0.7 I
e
2 per output
easy800-SWD: 0.15 to 0.35 per output
Maximum, total short-circuit current
A
easy800 standard: 8
Peak short-circuit current
A
easy800 standard:16
in the event of short-circuit
on attempted restart of device after 10 s
A
easy800-SWD: 10A/80 ms
easy800-SWD: 10A/20ms
Thermal cutout
easy800 standard: yes
easy800-SWD: no
Max. switching frequency of resistive load
depending on cycle time
Parallel wiring capability of outputs
easy800 standard: yes
easy800-SWD: no
with resistive load, with inductive load
with external suppressor circuit (see
section Connecting transistor outputs),
with combination within a group
Group 1: Q1 to Q4
Group 2: Q5 - Q8
Number of outputs (max.)
4
Max. total current
Caution!
Outputs must be actuated simultaneously
and for the same time duration.
A
2
Status display of the outputs
easy800 standard: LCD display
(if provided)
easy800-SWD: LED
T
0.95
≈
3 T
0.65
= 3
L
R
T
0.95
= 1 ms
R = 48
Ω
L = 16 mH
Utilization factor per group g =
0.25
Relative duty factor
%
100
Max. switching frequency
f = 0.5 Hz
Max. duty factor
DF = 50 %
Switching
operations/h
1500
EASY8..-DC-T..., easy800-SWD