3 Commissioning
3.6 Defining 800-SWD inputs/outputs
76
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
3.6 Defining
800-SWD inputs/outputs
EASY806-DC-SWD provides four local inputs. This is the factory setting.
Inputs I3 and I4 can be operated alternatively as outputs Q1 and Q2.
A display and operating facility is required to reconfigure the inputs as
outputs (
page 64). Proceed as follows to define the inputs and outputs:
▶
Simultaneously press the DEL and ALT buttons with the Status display
active.
▶
Use the cursor buttons to select the System menu item.
▶
Confirm with OK.
▶
Use the cursor buttons to select the ACTIVATE Q1 menu item.
▶
Confirm with OK.
▶
Use the cursor buttons to select the ACTIVATE Q2 menu item.
▶
Confirm with OK.
A tick appears behind the ACTIVATE Q1 menu item, indicating that I3 is
configured as an output. The same applies to Q2. You can now use the
outputs in the circuit diagram.
→
Be aware that certain function blocks may not be available with
certain configurations. For example, output Q2 is permanently
associated with PO01. If Q2 is configured as an input, PO01 is
no longer available.