![Delphin ProfiMessage Hardware Manual Download Page 241](http://html1.mh-extra.com/html/delphin/profimessage/profimessage_hardware-manual_2471098241.webp)
Profi
Message
External divider for analogue inputs and measurement range
±25 V or ±20 V
An extended measurement range of ±25 V or ±20 V can be achieved with a sym-
metrical external resistor divider. The recommended wiring appears as follows:
The resistor accuracy class should be (depending on requirements) 0.1% to 1%.
Input impedance is reduced here to 25 or 20 k
Ω
. Measuring point scaling must be
increased using the DataService Configurator PC software by the factor 2.5 or 2.0.
External AC coupling
AC coupling can be achieved with symmetrical capacitors. The recommended wir-
ing appears as follows:
Non-polarized capacitors must be used. The input high-pass has a cut-off fre-
quency of 4 … 0.4 Hz.
External AC coupling is useful for mobile systems. For fixed installations, refer to
AC coupling for analogue inputs
.
External power supply for ICP
®
/ IEPE acceleration sensors
Basic feed and coupling of measurement signals can be achieved with three com-
ponents. The recommended wiring appears as follows:
241
Delphin Technology AG
Dezember 2015
Profi
Message Manual
Summary of Contents for ProfiMessage
Page 1: ......
Page 31: ...ProfiMessage 3 5 4 ADIT 31 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Page 32: ...ProfiMessage 3 5 5 ADVT 3 5 6 AMDT 32 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Page 33: ...ProfiMessage 3 5 7 DIOT 3 5 8 IOIT 33 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Page 314: ...ProfiMessage 314 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Page 322: ......