![Delphin ProfiMessage Hardware Manual Download Page 140](http://html1.mh-extra.com/html/delphin/profimessage/profimessage_hardware-manual_2471098140.webp)
Profi
Message
Pause
: Pauses the program's execution, i.e. the current setpoint is retained for as
long as the specified channel has the set
Level
. The break pause channel has a
higher priority than the start channel, i.e. the start channel does not start the pro-
grammer while pause state is active.
For
Edge
settings, the setpoint is retained from the onset of the edge until the next
edge. An event here is also unable to give priority to a start channel over a pause
state.
Reset
: A reset event from the specified channel sets the program to the beginning
but does not start it. The reset channel has the highest priority, i.e. the reset con-
dition prevents starting by a start event and cancels a pause state.
Table
tab
The setpoint table creates a conditional procedure (event) with reference points
set by value pairs of time and a value. Each row of the table describes a program
step with a
time
t (fixed or variable) and a
value
y (fixed or variable). Based on the
previous value of yi-1 , the ti value indicates how long will it take to reach the yi
value. The first row defines the starting point of the event, so at least two value
pairs need to be entered. If a variable is used, it requires configuring via the
Vari-
ables
tab. This applies even when using a global (external) setpoint table for the
selected channel.
140
Delphin Technology AG
Dezember 2015
Profi
Message Manual
Summary of Contents for ProfiMessage
Page 1: ......
Page 31: ...ProfiMessage 3 5 4 ADIT 31 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Page 32: ...ProfiMessage 3 5 5 ADVT 3 5 6 AMDT 32 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Page 33: ...ProfiMessage 3 5 7 DIOT 3 5 8 IOIT 33 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Page 314: ...ProfiMessage 314 Delphin Technology AG Dezember 2015 ProfiMessage Manual ...
Page 322: ......