Profi
Message
6
Connection examples
This Section shows you connection examples of typical sensors and actuators. It
explains the available connection options and how to configure your sensors and
actuators.
Topics
6.1 Connecting sensors
Measuring voltage at analogue input
Sensors with voltage signal can be directly connected.
The largest measurement range is ± 10V bipolar or 10 V uni-
polar.
The smallest range is ± 156mV bipolar and 156 mV unipolar.
Measuring 20 mA current at analogue input
For sensors with current signals you must connect what is known as a load res-
istor to the device input terminals. Suitable resistors are available as accessories.
Measuring temperatures with a thermocouple at analogue
input
207
Delphin Technology AG
Dezember 2015
Profi
Message Manual