![Delphin ProfiMessage Hardware Manual Download Page 126](http://html1.mh-extra.com/html/delphin/profimessage/profimessage_hardware-manual_2471098126.webp)
Profi
Message
Controller type
K
TN
TV
PID
0.4 / (KI * Tu)
3.2 * Tu 0.8 * Tu
4.7.14.3
Configuring PID controllers
The controller is specifically configured in tabs “Main settings”, “Controller 1” and
“Controller 2”.
Settings in tabs “Controller 1” and “Controller 2” are only required for specific
applications.
The controller channel obtains its input values (setpoint variable ”W” and process
variable “X” from two HW channels or SW channels of the device). The controller
yields the manipulated variable “Y” as the output value in the preset value range
0...100% or -100..+100%. If you link the output of the controller channel directly
with an analogue output, you must enter the same scaling 0...100 % or -
100...+100 %.