NB!
In remote operation (parameter 002
Local/remote op-
eration
) the start/stop state at the time of mains con-
nection will depend on the external control signals. If
Pulse start
[8] is selected in parameter 302
Digital in-
put
, the motor will remain stopped after mains con-
nection.
020
Lock for Hand mode
Value:
Not active (DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter you can select whether it should be possible or not to
switch between Auto- and Hand mode. In Auto mode the frequency con-
verter is controlled by external signals whereas the frequency converter
in Hand mode is controlled via a local reference directly from the control
unit.
Description of choice:
If
Not active
[0] is selected in this parameter, the Hand mode function
will be inactive. This blocking can be activated as desired. If
Active
[1] is
selected you can switch between Auto- and Hand mode.
NB!
This parameter is only valid for LCP 2.
024
Userdefined Quick Menu
Value:
Not active (Disable)
[0]
Active (Enable)
[1]
Function:
In this parameter you can select the standard setup of the Quick menu
key on the control panel and the LCP 2 control panel.
Using this function, in parameter 025
Quick Menu setup
the user can
select up to 20 parameters for the Quick Menu key.
Description of choice:
If
not active
[0] is selected, the standard setup of the Quick Menu key is
active.
If
Active
[1] is selected, the user-defined Quick Menu is active.
025
Quick Menu setup
Value:
[Index 1 - 20] Value: 0 - 999
000
Function:
In this parameter you define which parameters are required in the Quick
Menu when parameter 024
User-defined Quick Menu
is set to
Active
[1].
Up to 20 parameters can be selected for the user-defined Quick Menu.
NB!
Please note that this parameter can only be set using
an LCP 2 control panel. See
Order form
.
Description of choice:
The Quick Menu is set up as follows:
1.
Select parameter 025
Quick Menu setup
and press [CHANGE
DATA].
2.
Index 1 indicates the first parameter in Quick Menu. You can
scroll between the index numbers using the [+ / -] keys. Select
Index 1.
3.
Using [< >] you can scroll between the three figures. Press the
[<] key once ad the last number in the parameter number can
be selected using the [+ / -] keys. Set Index 1 to 100 for pa-
rameter 100
Configuration
.
4.
Press [OK] when Index 1 has been set to 100.
5.
Repeat steps 2 - 4 until all parameters required have been set
to the Quick Menu key.
6.
Press [OK] to complete the Quick Menu setup.
If parameter 100
Configuration
is selected at Index 1, Quick Menu will
start with this parameter every time Quick Menu is activated.
Please note that parameter 024
User-defined Quick Menu
and parameter
025
Quick Menu setup
are reset to the factory setting during initialisation.
026
LED Status
Value:
Overload (Overload)
[0]
Therm. warn/alarm 36 (Overtemp)
[1]
Thermistor/ETR (Thermal Motor)
[2]
Digital input 18 (Digital Input 18)
[3]
Digital input 19 (Digital Input 19)
[4]
Digital input 27 (Digital Input 27)
[5]
Digital input 29 (Digital Input 29)
[6]
Digital input 33 (Digital Input 33)
[7]
As relay par. 323 (As relay / P323)
[8]
As dig.outp. par. 341 (Ad Dig. Out. / P341)
[9]
As mech.brake output
(As mech. brake output)
[10]
Function:
This parameter enables the user to visualize different situations using the
Status LED.
Description of choice:
Select the function to be visualized.
VLT
®
Decentral FCD 300 Design Guide
4 Programming
MG.90.S1.02 - VLT
®
is a registered Danfoss trademark
71