Conversion table
Conversion
index
Conversion
factor
73
0.1
2
100
1
10
0
1
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
-5
0.00001
4.7.5 Process Words
The block of process words is divided into two blocks of 16 bits, which
always occur in the defined sequence.
PCD 1
PCD 2
Control telegram
(master
⇒
slave)
Control word
Reference-
value
Control telegram
(slave
⇒
master)
Status word
Present outp.
frequency
4.7.6 Control Word According to FC Protocol
To select
FC protocol
in the control word, parameter 512
Telegram Pro-
file
must be set to
FC protocol
[1].
The control word is used to send commands from a master (e.g. a PC) to
a slave (frequency converter).
Bit
Bit = 0
Bit =1
00
Preset ref. lsb
01
Preset ref. msb
02
DC braking
03
Coasting stop
04
Quick stop
05
Freeze outp. freq.
06
Ramp stop
Start
07
Reset
08
Jog
09
Ramp 1
Ramp 2
10
Data not valid
Data valid
11
No function
Relay output
12
No function
Digital output
13
Select Setup, lsb
14
Select Setup, msb
15
Reversing
Bit 00/01:
Bit 00/01 is used to select between the two pre-programmed references
(parameters 215-218
Preset reference
) according to the following table:
Preset ref.
Parameter
Bit 01
Bit 00
1
215
0
0
2
216
0
1
3
217
1
0
4
218
1
1
NB!
In parameter 508
Selection of preset reference
a se-
lection is made to define how Bit 00/01 gates with the
corresponding function on the digital inputs.
Bit 02, DC brake:
Bit 02 = '0' causes DC braking and stop. Brake voltage and duration are
preset in parameters 132
DC brake voltage
and parameter 126
DC brak-
ing time
. Note: In parameter 504
DC brake
a selection is made to define
how Bit 02 gates with the corresponding function on a digital input.
Bit 03, Coasting stop:
Bit 03 = '0' causes the frequency converter to immediately "let go" of the
motor (the output transistors are "shut off"), so that it coasts to a stand-
still.
Bit 03 = '1' causes the frequency converter to be able start the motor if
the other starting conditions have been fulfilled. Note: In parameter 502
Coasting stop
a selection is made to define how Bit 03 gates with the
corresponding function on a digital input.
Bit 04, Quick stop:
Bit 04 = '0' causes a stop, in which the motor's speed is ramped down to
stop via parameter 212
Quick stop ramp-down time
.
VLT
®
Decentral FCD 300 Design Guide
4 Programming
MG.90.S1.02 - VLT
®
is a registered Danfoss trademark
103