![Danfoss VLT Decentral FCD 300 Design Manual Download Page 138](http://html1.mh-extra.com/html/danfoss/vlt-decentral-fcd-300/vlt-decentral-fcd-300_design-manual_3770840138.webp)
5.3.3 Spare Parts
The complete electronic part can be used as a spare part. The following four parts can replace all FCD 303-330 with and without Profibus.
For servicing DeviceNet and AS-interface units an additional control card is required to upgrade the electronic spare part.
FCD 303
178B1484
FCD 307
178B1485
FCD 315
178B1486
FCD 330
178B2301
The parts can be downsized one size simply by selecting the correct motor size, and the Profibus functionality can be changed/eliminated in Parameter
678.
The control card can also be replaced for repair of the electronic part.
Profibus, 12 MB control card
175N2338
DeviceNet control card
175N2325
AS-interface control card
175N2324
For servicing the installation box a kit containing various parts, plugs, and terminal PCB can be ordered 175N2121.
Service tool kit 175N2404
It is normally not possible to operate the FCD300 with open lid. Using the service tool kit, the electronic part and the installation box can be connected
without joining them. This might be helpful if measurements on input/output terminals are required during servicing.
5.4 General Technical Data
Mains supply (L1, L2, L3):
Supply voltage
3 x 380/400/415/440/480 V ±10%
Supply frequency
50/60 Hz
Max. imbalance on supply voltage
± 2.0% of rated supply voltage
Power factor (400 V) / cos.
Φ
1
0.90 / 1.0 at rated load
Number of connections at supply input L1, L2, L3
2 times/min.
Max. short-circuit value fuses
100,000 A
Max. short-circuit value circuit brakers
10,000 A
See Special Conditions section in the Design Guide
Output data (U, V, W):
Output voltage
0 - 100% of supply voltage
Output frequency
0.2 - 132 Hz, 1 - 1000 Hz
Rated motor voltage, 380-480 V units
380/400/415/440/460/480 V
Rated motor frequency
50/60 Hz
Switching on output
Unlimited
Ramp times
0.02 - 3600 sec.
Torque characteristics:
Starting torque (parameter 101 Torque characteristic = Constant torque)
160% in 1 min.
*
Starting torque (parameter 101 Torque characteristics = Variable torque)
160% in 1 min.
*
Starting torque (parameter 119
High starting torque
)
180% for 0.5 sec.
*
Overload torque (parameter 101 Torque characteristic = Constant torque)
160%
*
Overload torque (parameter 101 Torque characteristic = Variable torque)
160%
*
*Percentage relates to frequency converter's nominal current.
VLT
®
Decentral FCD 300 Design Guide
5 All About FCD 300
MG.90.S1.02 - VLT
®
is a registered Danfoss trademark
137