Output frequency x scaling [-]
equals the present output frequency f
M
multiplied by the factor set in parameter 008
Display scaling of output
frequency
.
Motor current [A]
gives the phase current of the motor measured as an
effective value.
Torque [%]
denotes the motor's present load in relation to the motor's
rated torque.
Power [kW]
gives the present power that the motor is absorbing in kW.
Power [HP]
gives the present power that the motor is absorbing in HP.
Motor voltage[V]
gives the voltage supplied to the motor.
DC link voltage [V]
gives the intermediate circuit voltage of the frequency
converter.
Thermal load motor [%]
gives the calculated/estimated load on the mo-
tor. 100 % is the cut-out limit.
Thermal load [%]
gives the calculated/estimated thermal load on the
frequency converter. 100 % is the cut-out limit.
Running hours [Hours]
gives the number of hours that the motor has tun
since the last reset in parameter 619
Reset of running hours counter
.
Digital input [Binary code]
gives the signal status from the 5 digital inputs
(18, 19, 27, 29 and 33). Terminal 18 corresponds to the bit on the ex-
treme left. `0' = no signal, `1' = signal connected.
Analog input 53 [V]
gives the voltage value of terminal 53.
Analog input 60 [mA]
gives the present value of terminal 60.
Pulse input 33[Hz]
gives the frequency in Hz connected to terminal 33.
External reference [%]
gives the sum of external references as a per-
centage (sum of analogue/pulse/serial communication) in the range from
Minimum reference, Ref
MIN
to Maximum reference, Ref
MAX
.
Status word [Hex]
gives one or several status conditions in a Hex code.
See
Serial communication
in the
Design Guide
for further information.
Heatsink temp.[°C]
gives the present heatsink temperature of the fre-
quency converter. The cut-out limit is 90-100 °C, while cutting back in
occurs at 70 ± 5 °C.
Alarm word [Hex]
gives one or several alarms in hex code. See
Serial
communication
in the
Design Guide
for further information.
Control word [Hex]
gives the control word for the frequency converter.
See
Serial communication
in the
Design Guide
for further information.
Warning word [Hex]
gives one or several warnings in hex code. See
Serial
communication
in the
Design Guide
for further information.
Extended status word [Hex]
gives one or several status modes in Hex
code. See
Serial communication
in the
Design Guide
for further informa-
tion.
Communication option card warning [Hex]
gives a warning word if there
is a fault in the communication bus. Only active if communication options
are installed.
If there are no communication options 0 Hex is displayed.
Pulse input 29[Hz]
gives the frequency in Hz connected to terminal 29.
Pulse count
gives the number of pulses that the unit has registered.
010
Small display line 1.1
Value:
See par. 009
Large display readout
Analog input 53 [V] [17]
Function:
In this parameter, the first of three data values can be selected that is to
be displayed in the LCP control unit display, line 1, position 1. This is a
useful function, e.g. when setting the PID regulator, as it gives a view of
process reactions to reference changes. The display readout is activated
by pushing the [DISPLAY STATUS] key.
Description of choice:
See parameter 009
Large display readout
.
011
Small display readout 1.2
Value:
See parameter 009
Large display readout
Motor current [A][6]
Function:
See the functional description given under parameter 010
Small display
readout
.
Description of choice:
See parameter 009
Large display readout
.
012
Small display readout 1.3
Value:
See parameter 009
Large display readout
Feedback [unit] [3]
Function:
See the functional description given under parameter 010
Small display
readout
.
Description of choice:
See parameter 009
Large display readout
.
013
Local control
Value:
Local not active (DISABLE)
[0]
Local control and open loop without slip compensation
(LOC CTRL/OPEN LOOP)
[1]
Remote-operated control and open loop without slip compensa-
tion
(LOC+DIG CTRL)
[2]
Local control as parameter 100
(LOC CTRL/AS P100)
[3]
Remote-operated control as parameter 100
(LOC+DIG CTRL/AS P100)
[4]
Function:
This is where the required function is selected if, in parameter 002
Local/
remote operation, Local operation
[1] has been chosen.
Description of choice:
If
Local not active
[0] is selected, it is not possible to set a reference via
parameter 003
Local reference
.
In order to enable a shift to
Local not active
[0], parameter 002
Local/
remote operation
must be set to
Remote operation
[0].
Local control and open loop
[1] is used if the motor speed is to be set via
parameter 003
Local reference
. When this choice is made, parameter 100
Configuration
automatically shifts to
Speed regulation, open loop
[0].
Remote-operated control and open loop
[2] functions in the same way as
Local control and open loop
[1]; however, the adjustable frequency drive
can also be controlled via the digital inputs.
For selections [1-2] control is shifted to open loop, no slip compensation.
Local control as parameter 100
[3] is used when the motor speed is to
be set via parameter 003
Local reference
, but without parameter 100
Configuration
automatically shifting to
Speed regulation, open loop
[0].
Remote-operated control as parameter 100
[4] works the same way as
Local control as parameter 100
[3]; however, the adjustable frequency
drive can also be controlled via the digital inputs.
Shifting from
Remote operation
to
Local operation
in parameter 002
Lo-
cal/remote operation
, while this parameter has been set to
Remote-
operated control and open loop
[1]: The present motor frequency and
VLT
®
Decentral FCD 300 Design Guide
4 Programming
MG.90.S1.02 - VLT
®
is a registered Danfoss trademark
69
4