512
Telegram Profile
Value:
Profidrive (Profidrive)
[0]
FC protocol (FC protocol)
[1]
Fast I/O FC-profile (Fast I/O FC-profile)
[2]
Function:
It is possible to choose between three different control word profiles.
Description of choice:
Select the desired control word profile.
See
Serial port for FCD 300
for further details of control word profiles.
513
Bus time interval
Value:
1 - 99 sec.
1 sec.
Function:
In this parameter it is possible to preset the maximum time expected to
elapse between receipt of two consecutive telegrams. If this time is ex-
ceeded, the serial communication is assumed to have stopped and the
desired reaction is preset in parameter 514
Bus time interval function
.
Description of choice:
Preset the required time.
514
Bus time interval function
Value:
Off (off)
[0]
Freeze output frequency (FREEZE OUTPUT)
[1]
Stop (STOP)
[2]
Jogging (JOGGING)
[3]
Max. speed (MAX SPEED)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
In this parameter you can select the required reaction for the frequency
converter when the preset time in parameter 513
Bus time interval
has
been exceeded. If choices [1] to [5] are activated the output relay will be
deactivated.
Description of choice:
The output frequency of the frequency converter can be frozen at the
present value, stop the motor, be frozen at parameter 213
Jogging fre-
quency
, be frozen at parameter 202
Output frequency, high limit f
MAX
or stop and activate a cut out.
4 Programming
VLT
®
Decentral FCD 300 Design Guide
112
MG.90.S1.02 - VLT
®
is a registered Danfoss trademark
4