4.9 Parameter Group 6-** Technical Functions
600-605 Operating Data
Value:
Par. no.
Description
Display text
Unit
Range
600
Operating hours
(OPERATING HOURS)
Hours
0-130,000.0
601
Hours run
(RUNNING HOURS)
Hours
0-130,000.0
602
kWh counter
(KWH COUNTER)
kWh
Depends on unit
603
Number of power-up's
(POWER UP'S)
Number of times
0-9999
604
Number of overtemperatures
(OVER TEMP'S)
Number of times
0-9999
605
Number of overvoltages
(OVER VOLT'S)
Number of times
0-9999
Function:
These parameters can be read out via the serial communication port and
the LCP control unit.
Description of choice:
Parameter 600, Operating hours:
Gives the number of hours the frequency converter has been operating.
The value is saved every hour and when there is a mains failure. This
value cannot be reset.
Parameter 601, Hours run:
Gives the number of hours the motor has been operating since the reset
in parameter 619
Reset of hours-run counter
. The value is saved every
hour and when there is a mains failure.
Parameter 602, kWh counter:
Gives the frequency converter's output energy in kWh. The calculation is
based on the mean kW value over one hour. This value can be reset using
parameter 618
Reset of kWh counter
.
Range: 0 - depends on unit.
Parameter 603, Number of power-ups:
Gives the number of power-ups of the supply voltage undertaken on the
frequency converter.
Parameter 604, Number of overtemperatures:
Gives the number of overtemperature faults that have been registered on
the frequency converter's heat sink.
Parameter 605, Number of overvoltages:
Gives the number of overvoltages of the intermediate circuit voltage in
the frequency converter. This is only counted when Alarm 7
Overvoltage
is active.
NB!
Parameters 615-617
Fault log
cannot be read out via
the integral control unit.
615
Fault log: Error code
Value:
[Index 1 - 10] Error code: 0 - 99
Function:
In this parameter it is possible to see the reason for a trip (cut-out of the
frequency converter) occurring. 10 [1-10] log values are defined.
The lowest log number [1] contains the latest/most recently saved data
value. The highest log number [10] contains the oldest data value saved.
If a trip occurs, it is possible to see the cause, time and a possible value
of the output current or output voltage.
Description of choice:
Given as a fault code, in which the number refers to a table. See the table
in
Warnings/alarm messages
.
616
Fault log: Time
Value:
[Index 1 - 10] Hours: 0 - 130,000.0
Function:
In this parameter it is possible to see the total number of operating hours
in connection with the last 10 trips.
10 [1-10] log values are denoted. The lowest log number [1] contains the
latest/most recently saved data value, and the highest log number [10]
contains the oldest data value.
Description of choice:
Read out as one value.
617
Fault log: Value
Value:
[Index 1 - 10] Value: 0 - 9999
Function:
In this parameter it is possible to see at which value a trip occurred. The
unit of the value depends on which alarm is active in parameter 615
Fault
log: Fault code
.
Description of choice:
Read out as one value.
618
Reset of kWh counter
Value:
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Resetting parameter 602
kWh counter
to zero.
Description of choice:
If
Reset
[1]is selected and you press the [OK] key, the frequency con-
verter's kWh counter is reset to zero. This parameter cannot be selected
via serial communication.
NB!
When the [OK] key is activated, the counter is reset to
zero.
619
RESET RUNNING HOURS COUNTER
Value:
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
VLT
®
Decentral FCD 300 Design Guide
4 Programming
MG.90.S1.02 - VLT
®
is a registered Danfoss trademark
115
4