Mechanical brake with accelerator winding
Par. 302
Digital input
=
Start
[7]
Par. 304
Digital input
=
Coasting stop inverted
[2]
See also par. 138, 139, 140
Use of the relay for 230 V AC brake
Par. 302
Digital input
=
Start
[7]
Par. 304
Digital input
=
Coasting stop inverted
[2]
Par. 323
Relay output
=
Mechanical brake control
[25]
See also par. 138, 139, 140
Mechanical brake control
[25] = '0' => Brake is closed.
Mechanical brake control
[25] = '1' => The brake is open.
See more detailed parameter settings under
Control of mechanical brake
.
NB!
Do not use the internal relay for DC brakes or brake voltages > 250 V.
3.6.10 Counter Stop via Terminal 33
The start signal (terminal 18) must be active, i.e. logical '1', until the out-
put frequency is equal to the reference. The start signal (terminal 18 =
logical '0') must then be removed before the counter value in parameter
344 has managed to stop the VLT frequency converter.
Par. 307
Digital input
=
Pulse input
[30]
Par. 343
Precise stop function
=
Counter stop with reset
[1]
Par. 344
Counter value
= 100000
VLT
®
Decentral FCD 300 Design Guide
3 Installation
MG.90.S1.02 - VLT
®
is a registered Danfoss trademark
59