The FCD 300 holds a log with valuable information on failure. Information on the most recent 10 faults is stored and indexed in three different parameters
to help diagnosis.
Illustration 5.1: LCP2-plug
Parameter 616
stores the time of the fault as measured by the internal
clock.
Paramet er 617
holds a fault code telling the type of fault detected.
Parameter 618
stores a measurement relevant for the case. Typically
the intermediate circuit voltage or output current measured immediately
before failure.
Illustration 5.2: Local Control Panel
No
Name
Colour
OK status
Alternatives
Function
1
Status
Yellow
Off
Off
Status of the FCD is OK
On
Corresponding to parameter setting. For further information see
Design Guide
-
parameter number 26 and DeviceNet manual for specific DeviceNet signalling
2
Bus
Green
On (If bus
option is
present,
else Off)
On
OK status for the fild bus used
(Not relevant for non field bus device)
Slow flashing
Local operation or local stop
Fast flashing
Interface working, but no communication with master
(See field bus manual for specific info)
(Not relevant for non field bus device)
Off
Status for the field bus
not
OK
(not relevant for non field bus device)
3
Alarm
Red
Off
Off
No alarm is present
Flashing
Flashing while trip/trip lock is present
4
Warning
Yellow
Off
Off
No warning is present
Flashing
Flashing while warning situation is present
5
On
Green
On
On
The unit is supplied by mains power or 24 V DC
Off
Mains power or 24 V DC is missing
Table 5.1: LED diagnostics on decentralised FCD 300
VLT
®
Decentral FCD 300 Design Guide
5 All About FCD 300
MG.90.S1.02 - VLT
®
is a registered Danfoss trademark
133