PNU #
Parameter-description
Factory setting
Changes during
operation
4-setup
Conv. index Data-type
100
Configuration
Speed reg., open loop
No
Yes
0
5
101
Torque characteristics
Constant torque
Yes
Yes
0
5
102
Motor power P
M,N
depends on unit
No
Yes
1
6
103
Motor voltage U
M,N
depends on unit
No
Yes
-2
6
104
Motor frequency f
M,N
50 Hz
No
Yes
-1
6
105
Motor current I
M,N
depends on motor selected
No
Yes
-2
7
106
Rated motor speed
depends on par. 102
No
Yes
0
6
107
Automatic motor adjustment
Optimisation off
No
Yes
0
5
108
Stator resistance R
S
depends on motor selected
No
Yes
-3
7
109
Stator reactance X
S
depends on motor selected
No
Yes
-2
7
117
Resonance dampening
0 %
Yes
Yes
0
5
119
High start torque
0.0 sec
No
Yes
-1
5
120
Start delay
0.0 sec
No
Yes
-1
5
121
Start function
Coast in start del.
No
Yes
0
5
122
Function at stop
Coast
No
Yes
0
5
123
Min. freq. for activation of par. 122
0.1 Hz
No
Yes
-1
5
126
DC braking time
10 sec.
Yes
Yes
-1
6
127
DC brake engaging frequency
OFF
Yes
Yes
-1
6
128
Thermal motor protection
No protection
Yes
Yes
0
5
130
Start frequency
0.0 Hz
No
Yes
-1
5
131
Voltage at start
0.0 V
No
Yes
-1
6
132
DC brake voltage
0%
Yes
Yes
0
5
133
Start voltage
depends on unit
Yes
Yes
-2
6
134
Load compensation
100 %
Yes
Yes
-1
6
135
U/f-ratio
depends on unit
Yes
Yes
-2
6
136
Slip compensation
100 %
Yes
Yes
-1
3
137
DC hold voltage
0%
No
Yes
0
5
138
Brake cut out value
3.0 Hz
Yes
Yes
-1
6
139
Brake cut in frequency
3.0 Hz
Yes
Yes
-1
6
140
Current, minimum value
0%
No
Yes
0
5
142
Leak reactance
depends on motor selected
No
Yes
-3
7
144
AC brake factor
1.30
No
Yes
-2
5
146
Reset voltage vector
Off
Yes
Yes
0
5
147
Motor type
General
PNU #
Parameter
description
Factory setting
Changes during
operation
4-setup
Conv.
index
Data
type
200
Output frequency range
Clockwise only, 0-132 Hz
No
Yes
0
5
201
Output frequency,
low limit f
MIN
0.0 Hz
Yes
Yes
-1
6
202
Output frequency,
high limit f
MAX
132 Hz
Yes
Yes
-1
6
203
Reference range
Min ref.-Max ref.
Yes
Yes
0
5
204
Minimum ref Ref
MIN
0.000 Hz
Yes
Yes
-3
4
205
Maximum ref Ref
MAX
50.000 Hz
Yes
Yes
-3
4
206
Ramp type
Linear
Yes
Yes
0
5
207
Ramp-up time 1
3.00 sec.
Yes
Yes
-2
7
208
Ramp-down time 1
3.00 sec.
Yes
Yes
-2
7
209
Ramp-up time 2
3.00 sec.
Yes
Yes
-2
7
210
Ramp-down time 2
3.00 sec.
Yes
Yes
-2
7
211
Jog ramp time
3.00 sec.
Yes
Yes
-2
7
212
Quick stop ramp-down time
3.00 sec.
Yes
Yes
-2
7
213
Jog frequency
10.0 Hz
Yes
Yes
-1
6
214
Reference function
Sum
Yes
Yes
0
5
215
Preset reference 1
0.00%
Yes
Yes
-2
3
216
Preset reference 2
0.00%
Yes
Yes
-2
3
217
Preset reference 3
0.00%
Yes
Yes
-2
3
218
Preset reference 4
0.00%
Yes
Yes
-2
3
219
Catch up/slow down
reference
0.00%
Yes
Yes
-2
6
221
Current limit
160 %
Yes
Yes
-1
6
223
Warn. Low current
0.0 A
Yes
Yes
-1
6
224
Warn. High current
I
MAX
Yes
Yes
-1
6
225
Warn. Low frequency
0.0 Hz
Yes
Yes
-1
6
226
Warn. High frequency
132.0 Hz
Yes
Yes
-1
6
227
Warn. Low Feedback
-4000.000
Yes
Yes
-3
4
228
Warn. High Feedback
4000.000
Yes
Yes
-3
4
229
Frequency bypass,
bandwidth
0 Hz (OFF)
Yes
Yes
0
6
230
Frequency bypass 1
0.0 Hz
Yes
Yes
-1
6
231
Frequency bypass 2
0.0 Hz
Yes
Yes
-1
6