3.6.8 Preset References
Switch between 8 preset references via two digital inputs and Setup 1 and Setup 2.
Par. 004
Active Setup
=
Multisetup 1
[5]
Par. 204
Min. reference
= 0 Hz
Par. 205
Max. reference
= 50 Hz
Par. 302
Digital input
=
Start
[7]
Par. 303
Digital input
= Choice of Setup, lsb [31]
Par. 304
Digital input
=
Coasting stop inverted
[2]
Par. 305
Digital input
= Preset ref., lsb [22]
Par. 307
Digital input
= Preset ref., msb [23]
Setup 1
contains the following preset references:
Par. 215
Preset reference 1
= 5.00%
Par. 216
Preset reference 2
= 10.00%
Par. 217
Preset reference 3
= 25.00%
Par. 218
Preset reference 4
= 35.00%
Setup 2
contains the following preset references:
Par. 215
Preset reference 1
= 40.00%
Par. 216
Preset reference 2
= 50.00%
Par. 217
Preset reference 3
= 70.00%
Par. 218
Preset reference 4
= 100.00%
This table shows what the output frequency is:
Preset ref.,
msb
Preset ref., lsb Selection of
Setup
Output frequen-
cy[Hz]
0
0
0
2.5
0
1
0
5
1
0
0
10
1
1
0
17.5
0
0
1
20
0
1
1
25
1
0
1
35
1
1
1
50
3.6.9 Connection of Mechanical Brake
Using terminal 122/123
Par. 302
Digital input
=
Start
[7]
Par. 304
Digital input
=
Coasting stop inverted
[2]
See also par. 138, 139, 140
3 Installation
VLT
®
Decentral FCD 300 Design Guide
58
MG.90.S1.02 - VLT
®
is a registered Danfoss trademark
3