been selected:
Frequency
,
Reference
,
Torque
and
Current
as readout in
the first and second line.
Display mode III:
This display mode is called up as long as the [DISPLAY / STATUS] key is
held down. When the key is released it switches back to Display mode II,
unless the key is held down for less than approx. 1 sec., in which case
the system always reverts to Display mode I.
50.0 Hz
SETUP
1
MOTOR IS RUNNING
REF% TORQUE CURR A
Here you can read out the parameter names and units for operating data
in the first and second lines. Line 2 in the display remains unchanged.
Display mode IV:
This display mode can be called up during operation if a change has to
be made in another Setup without stopping the frequency converter. This
function is activated in parameter 005
Programming Setup
.
50.0 Hz
SETUP
1
MOTOR IS RUNNING
REF% TORQUE CURR A
Here the programming Setup number 2 will flash to the right of the active
Setup.
4.1.7 Parameter Setup
A frequency converter's comprehensive work area can be accessed via a
large number of parameters, making it possible to adapt its functionality
for a specific application. To provide a better overview of the many pa-
rameters, there is a choice of two programming modes - Menu mode and
Quick Menu mode. The former provides access to all parameters. The
latter takes the user through the parameters, which make it possible to
start operating the frequency converter in most cases, in accordance with
the Setup made. Regardless of the mode of programming, a change of a
parameter will take effect and be visible both in the Menu mode and in
the Quick menu mode.
Structure for Quick menu mode v Menu mode
In addition to having a name, each parameter is linked up with a number
which is the same regardless of the programming mode. In Menu mode,
parameters will be split into groups, with the first digit (left) of the pa-
rameter number indicating the group number of the parameter in ques-
tion.
•
Using the [QUICK MENU] key, it is possible to get access to the
most important parameters of the frequency converter. After
programming, the frequency converter is in most cases ready
for operation. Scroll through the Quick menu using the [+ / -]
keys and change the data values by pressing [CHANGE DATA]
+ [OK].
•
The Menu mode allows choosing and changing all parameters
as required. However, some parameters will be "shaded off",
depending on the choice in parameter 100
Configuration
.
4.1.8 Quick Menu with LCP 2 Control Unit
Start Quick Setup by pressing the [QUICK MENU] key, which will bring
out the following display values:
50.0 Hz
SETUP
1
QUICK MENU X OF Y
001 LANGUAGE
ENGLISH
At the bottom of the display, the parameter number and name are given
together with the status/value of the first parameter under the Quick
menu. The first time the [QUICK MENU] key is pressed after the unit has
been switched on, the readouts always start in pos. 1 - see table below.
Pos.
Parameter no.
Unit
1
001 Language
2
102 Motor power
[kW]
3
103 Motor voltage
[V]
4
104 Motor frequency
[Hz]
5
105 Motor current
[A]
6
106 Rated motor speed
[rpm]
7
107 AMT
8
204 Minimum reference
[Hz]
9
205 Maximum reference
[Hz]
10
207 Ramp-up time
[sec]
11
208 Ramp-down time
[sec]
12
002 Local/remote operation
13
003 Local reference
[Hz]
4 Programming
VLT
®
Decentral FCD 300 Design Guide
64