Control for 6/8 HP Outdoor Unit
SiAF332111E
78
Part 4 Functions and Control
Radiation fin temperature control
This control is performed for each compressor.
2.6.5 Overload Protection Control
Prevent ignition due to abnormal heating of the compressor when it becomes damaged or
abnormal operation.
Condition
All compressors
A
more than 91 °C
B
less than 89 °C
C
more than 110 °C
Normal control
Fin temperature standby
Reduce compressor capacity
When occurring 4 times within 60
minutes, the error code
L4
is output.
A
B
C
Normal control
Overload standby
(Error code
F3
is output)
Compressor body temp.
125
°C
&
Compressor body temp.
110
°C
Remote controller resets.