Field Settings for Outdoor Unit (10/12 HP Models)
SiAF332111E
152
Part 5 Field Settings and Test Operation
Note(s)
Note(s)
Operating the BS buttons
By operating the BS buttons it is possible to:
Perform special actions (test run, etc).
Perform field settings (demand operation, low noise, etc).
Below procedure explains how to operate the BS buttons to reach the required mode in the
menu, select the correct setting and modify the value of the setting. This procedure can be used
any time special settings and regular field setting are discussed in this manual.
Setting definition:
Ex. [A-B]: C
A: mode
B: setting
C: setting value.
A, B and C are numerical values for field settings. Parameter C has to be defined. It can be a
chosen from a set (0, 1, 2, 3, 4, 5, …) or regarded as an ON/OFF (1 or 0) depending on the
contents. This is informed when the field setting is explained.
Functions of the BS button switches which are located on the outdoor unit main PCB
(A1P)
Turn ON the power supply of the outdoor unit and all indoor units.
When the communication between indoor units and outdoor unit(s) is established and normal,
the segment indication state will be as below (default situation when shipped from factory).
When turning ON the power supply: flashing as indicated. First checks on power supply are
executed (1~2 minutes).
When no trouble occurs: lighted as indicated (8~10 minutes).
Ready for operation: blank display indication as indicated.
Segment display indications:
When above situation cannot be confirmed after 12 minutes, the error code can be checked on
the indoor unit user interface and the outdoor unit segment display. Solve the error code
accordingly. The communication wiring should be checked at first.
INFORMATION: During special operation (e.g., test operation, etc.) or when an error
happened, information will contain letters and numerical values.
Off
Blinking
On
INFORMATION: During special operation (e.g., test operation, etc.) or when an error
happened, information will contain letters and numerical values.
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...