
Control for 6/8 HP Outdoor Unit
SiAF332111E
76
Part 4 Functions and Control
2.6.3 Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against an error or transient increase of discharge pipe temperature.
2.6.4 Inverter Protection Control
Inverter current protection control and radiation fin temperature control are performed to prevent
tripping due to an abnormality, or transient inverter overcurrent, and fin temperature increase.
Inverter overcurrent protection control by primary current [CTi1]
Normal control
Discharge pipe temperature > 135°C
Discharge pipe
temperature < 95°C
Discharge pipe
temperature > 108°C
Reduce compressor capacity step
Discharge pipe temperature standby
When occurring 3 times within 100
minutes, the error code
F3
is output.
(Sub code - 01)
Condition
Primary current [CTi1] (A)
Ta < 43 °C
Ta ≥ 43 °C
A
> 27.0
> CTi1 in graph A
B
≤ 25.0
≤ CTi1 in graph B
Normal control
Reduce compressor step
A
B
8
10
12
14
16
18
20
22
24
26
43
44
45
46
47
48
49
50
51
52
53
CTi1 (A)
Ta (°C)
Graph A
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...