Control for 6/8 HP Outdoor Unit
SiAF332111E
68
Part 4 Functions and Control
Note(s)
2. Control for 6/8 HP Outdoor Unit
2.1 Operation Flowchart
For detailed description of each function in the flow below, refer to the details on related function
on the following pages.
1. If the indoor unit stops or the thermostat turns OFF while in oil return control, pump down
residual operation is performed on completion of the oil return operation.
2. Not performed during cooling mode.
Stop control
(1) Abnormal shutdown
Standby control
(1) Restart standby
(2) Crankcase heater control
Startup control
(include pressure equalization before startup)
(1) Cooling startup control
Normal control
(1) List of functions in normal control
(2) Compressor control
(3) Compressor capacity control
(4) Compressor step control
(5) Electronic expansion valve control
(6) Step control of outdoor unit fans
Protection control
(1) High pressure protection control
(2) Low pressure protection control
(3) Discharge pipe protection control
(4) Inverter protection control
(5) Overload protection control
Thermostat ON
End of
startup
control
Abnormality
Thermostat OFF
Conditions met for oil return
Special control
(1) Pump down residual control
(note 2)
(2) Oil return control (note 1)
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...