Field Settings for Indoor Unit
SiAF332111E
104
Part 5 Field Settings and Test Operation
Note(s)
1.4.18 Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when sealing material
kit of air discharge outlet has been installed.) The second code No. is factory set to
01
.
: Factory setting
1.4.19 Swing Pattern Settings
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed
side by side are set to swing in an opposite direction to agitate airflow to reduce temperature
irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
: Factory setting
1.4.20 Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
1. Some indoor unit models are not equipped with draft prevention (upward) function.
2. When the model FXFSQ-AR is attached with a closing member kit, set the Second Code No.
to
02
or
03
.
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
1
01
4-way airflow
02
3-way airflow
03
2-way airflow
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
2
01
All direction synchronized swing
02
—
03
Facing swing
FXFSQ-AR, FXAQ-P
: Factory setting
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
4
01
Draft prevention (upward)
02
Standard
03
Ceiling soiling prevention (downward)
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...