Outline of Control (Indoor Unit)
Part 4 Functions and Control
87
Note(s)
3.9 Dew Condensation Prevention Control
3.9.1 FXFSQ-AR Models
Indoor operation under a certain condition will limit the swing range of the flaps.
Refer to the table below for flap action under this control.
3.9.2 FXAQ-P Models
In cooling and dry operation, the following control is carried out in order to prevent dew
condensation when the horizontal blade blows air downward.
Starting condition
Dew condensation prevention control
Dry operation with horizontal airflow (Position
C
) is carried out for 1 hour.
When there is any change to fan operation, airflow direction and operation ON/OFF state during
dew condensation prevention control, this control is canceled.
Dew condensation prevention control
Flap setting
OFF
In action
P0
P0
P1
P1
P1
P1
P2
P2
P2
P3
P3
P3
P4
P4
P4
Swing
P0 – P4
P1 – P4
Thermostat OFF
De
w
condensation
pre
v
ention control OFF
De
w
condensation
pre
v
ention control in action
Position P0 contin
u
es
for 30 min
u
tes.
P0
P1
P2
P3
P4
Indoor
u
nit
AIR
Flap position
(O
b
ser
v
ed horizontally)
FXAQ-P
Position
A
P4
B
(minutes)
20
Position
C
P3
● Horizontal blade is set to downward flow (Position
A
)
● Cooling operation (compressor operation) continues for
B
minutes.
&
P0
P1
P2
P3
P4
Indoor
u
nit
AIR
Flap position
(O
b
ser
v
ed horizontally)
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...