SiAF332111E
Control for 4/5/10/12 HP Outdoor Unit
Part 4 Functions and Control
57
1.2.2 Compressor PI Control
Carries out compressor capacity control to maintain Te at constant during cooling operation
thus ensuring stable unit performance.
Cooling operation
Controls compressor capacity to achieve target Te value (TeS).
Te: Low pressure equivalent saturation temperature (°C)
TeS: Target temperature of Te (Varies depending on Te setting, operating frequency,
etc.)
Compressor Frequency
4/5 HP
Depending on the operating conditions of the compressor, the compressor can be run in an
operating mode different from the modes listed in the table above.
Te setting (Setting mode 2)
(°C)
Lower
Normal
(Default)
Higher
3
6
7
8
9
10
11
Step
Frequency (Hz)
RXQ4ARV1
RXQ5ARV1
1
―
45
2
―
52.5
3
57
57
4
61.5
61.5
5
66
66
6
72
72
7
78
78
8
85.5
85.5
9
93
93
10
100.5
100.5
11
109.5
109.5
12
118.5
118.5
13
127.5
127.5
14
136.5
136.5
15
145.5
145.5
16
154.5
154.5
17
163.5
163.5
18
174
174
19
183
183
20
192
192
21
201
202.5
22
211.5
213
23
222
225
24
232.5
237
25
243
250.5
26
―
264
27
―
279
28
―
294
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...