Check
SiAF332111E
344
Part 6 Service Diagnosis
Note(s)
Reference
6.5 Wet Operation Check
CHECK 5
Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points.
1: Superheating temperature control in cooling is conducted by indoor unit electronic
expansion valve.
2: Guideline of superheating degree to judge as wet operation
(1) Suction gas superheating degree: Less than 3°C;
(2) Discharge gas superheating degree: Less than 15°C,
except immediately after compressor starts up or is running under dropping control.
(Use the above values as a guide. Depending on the other conditions, the unit may be normal
despite the values within the above range.)
CHECK 6
Refer to page 345.
Refrigerant stagnation
Overcharge of refrigerant
Defective crankcase heater
Frequent ON/OFF of compressor
[In cooling]
Indoor unit
electronic
expansion
valve opens too
much. (
∗
1)
Defective control
of superheating
degree
Defective
indoor unit
electronic
expansion
valve
Defective
control
Defective valve coil
Defective main PCB
Defective valve body
←
Refer to
CHECK 6
.
←
Are the coil resistance and
insulation normal?
←
Is the connector properly connected?
Are the thermistor resistance
characteristics normal?
←
Is the connector properly connected?
Are the thermistor resistance
characteristics normal?
←
Can the fan motor be rotated
with hands?
Are the motor coil resistance and
insulation normal?
←
Is the air filter clogged?
←
Is there any obstacle in the
airflow passage?
Wet operation
Degraded
evaporating
capacity
High
airflow
passage
resistance
Dirty evaporator
Decreased
airflow rate
Decreased
fan output
Defective fan motor
Dirty filter
Obstacles
←
Does the heat exchanger get clogged?
Defective main PCB
(including capacity
setting)
Defective gas pipe
thermistor of indoor unit
Defective liquid pipe
thermistor of indoor unit
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...